NetSure 7100 Series
Specifications
Technical Specifications
NetSure 7100 Series
- Product Overview
- Power Capacity
- 600 kW (6 bays)
- Current Capacity
- 12,000 A (6 bays)
- System Type
- Cabinet or Relay Rack
- Input
- Input Voltage, Nominal
- 208 VAC to 277/480 VAC
- Input Voltage, Operational
- 176 VAC to 305/528 VAC
- Input Connections
- Terminal Blocks or Line Cords
- Equipment Dimensions (H x W x D)
- D Cabinet:12.2" (7RU) to 33.25" (19RU) x 23" x 20.1", R Shelves:1.7" (1RU) or 5.2" (3RU) x 23" x 20.1"
- Access
- Front for installation, operation and maintenance, Rear for multi-bay, rectifier shelf or battery tray expansion
- Output
- Output Voltage, Nominal
- -48 VDC, +24 VDC, -58 VDC
- Output Voltage, Operational
- Rectifier: -42 VDC to -58 VDC; Converter: +24 VDC to +28 VDC or -56 VDC to -58 VDC
- Output Capacity
- Up to 2000 amps per bay at -48 VDC plus redundancy, maximum of six bays; Up to 520 amps at +24 VDC or -58 VDC plus redundancy
- Peak Efficiency
- Rectifier: 96.5%; Converter: 95% (+24 VDC or -58 VDC)
- Load Circuit Breakers / Fuses
- Up to (104) Bullet CBs, 1 to 300 A, Up to (24) GJ/218 CBs, 100 to 800 A, Up to (16) TPH Fuses, 70 to 600 A, Up to (16) TBL-B Fuses, 70 to 250 A
- Physical Characteristics
- Battery Circuit Breakers / Fuses
- Up to (24) Bullet CBs, 1 to 300 A, Up to (4) GJ/218 CBs, 100 to 800 A, Up to (4) TPH Fuses, 70 to 600 A /up to 200A CB Disconnect mounted on each batt
- Options
- Low Voltage Load Disconnect, Low Voltage Batttery Disconnect, Battery Shunt, Battery Trays - Pre-cabled, Bulk Output Panel, Up to (68) Temp Sensors
- Weight
- 90.9 to 295.5 kg
- Height
- 2134 mm
- Width
- 584.2 to 711.2 mm
- Depth
- 510.5 to 711.2 mm
- Environmetal & Standard Compliance
- Control and Monitoring
- Dual Ethernet, Embedded web pages, SNMP, Modbus, Battery Management, Programmable Relay Outputs and Binary Inputs, Energy Management
- Operating Temperature
- -40 °C to +40 °C (-40 °F to +104 °F)
- Safety Compliance
- UL 1801 Listed (“c UL”), NEBS Level 3
- EMC Compliance
- FCC Class B
- UM1R483500E Rectifier User Manual
- UM1R482000E3 eSure Rectifier User Manual
- IM582127000 NetSure 7100 Installation Manual
- UM02440103 SM-IO2 User Manual
- UM10010507 SM-DU+ User Manual
- IM559252 NetSure Controller Ethernet Kit
- UM1C48582000P3 eSure Power Extend Converter User Manual
- IM588820200SK001 NetSure Battery Tray Kit Installation Manual
- NetSure™ Control Unit (NCU) Controller 2nd Ethernet Port Retrofit Kit
- NetSure 7100 Data Sheet with eSure Power Extend Converters
- R48-3500e3 eSure Rectifier Data Sheet
- R48-3500e Rectifier Data Sheet
- C48/58-2000P3 eSure™ Power Extend Converter Data Sheet
- C48-24-1500 eSure Converter Data Sheet
- Distributed Antenna System Solutions (DAS)
- NCU Controller Data Sheet
- Vertiv™ NetSure™ DC Power Services Maintenance Data Sheet
- Vertiv™ NetSure™ DC Power Services Test & Turn-Up Data Sheet
*To see model-specific downloads, you will need to go to the model-specific product page by selecting the model name in the specifications chart above.