NetSure 5100 Integrated DC Power System
The NetSure 5100 Series, a compact -48 volt 150 A DC power solution, features an advanced control unit, up to (4) positions for 2000 W high-efficiency eSure rectifiers, and integrated distribution options. [Spec #582137200]
Guadar este produto no seu dashboard
Você pode guardar este produto no seu dashboard para ve-lo depois. Você pode elimina-lo com facilidade do seu dashboard quando você já no quer ve-lo lá.
Please login or create an account to save this for later
- Telecomunicação
NetSure 5100 Integrated DC Power System
The NetSure 5100 Series, a compact -48 volt 150 A DC power solution, features an advanced control unit, up to (4) positions for 2000 W high-efficiency eSure rectifiers, and integrated distribution options. [Spec #582137200]
- Telecomunicação
Vantagens
Recursos
Especificações
This highly flexible NetSure 5100 DC power system is available as an integrated version where space for rectifiers and distribution are available in the same shelf. These systems are optimal for rack-mounting in any building, shelter or cabinet installation. This system is easily integrated into a Vertiv outdoor enclosure when a pre-manufactured space efficient outdoor solution is needed. The system can also be shipped loose or mounted in a relay rack with battery trays. Our most compact NetSure 5100 system measures 2 RU high and has output current capability up through 150 A. Available in 19” and 23” widths, the system provides distribution space for GMT fuses up to 15 A or a combination of 150 A circuit breakers and GMT fuses. Configuration options include battery low voltage disconnect (BLVD), load low voltage disconnect (LLVD) or no low voltage disconnect.
- Product Overview
- Power Capacity
- 2 - 7.2 kW
- Current Capacity
- 40 - 150 A
- Input
- Input Voltage, Nominal
- Single phase: 120 VAC, 208 VAC to 240 VAC
- Input Voltage, Operational
- Rectifier: (Single Phase) 85 VAC to 300 VAC
- Input Connections
- Molex for AC cords or hardwiring
- Equipment Dimensions (H x W x D)
- up to 3U x (19" or 23") x 14.7"
- Access
- Front and Rear access
- Output
- Output Voltage, Nominal
- -48 VDC
- Output Voltage, Operational
- Rectifier: -42 VDC to -58 VDC
- Output Capacity
- Up to 150 amps at -48 VDC plus redundancy
- Peak Efficiency
- Rectifier: 96%
- Load Circuit Breakers / Fuses
- 1-150 A E/M or E bullet nose breakers or 1-15A GMT fuses
- Physical Characteristics
- Battery Circuit Breakers / Fuses
- 1A to 150 A E/M or E breakers
- Options
- Optional Battery Trays, SM-Temp, BAU, Relay racks
- Environmetal & Standard Compliance
- Control and Monitoring
- NCU with remote access via web browsers, TCP/IP & SNMP as standard
- Temperatura de Operação
- -40 °C to +65 °C ( 40 °F to +149 °F)
- Safety Compliance
- UL Listed (cUL)
- EMC Compliance
- Conforms to FCC rules Part 15, Subpart B, Class B; EN55022 Class B, radiated and conducted; GR-1089 Issue 4